SULFUR HEXAFLUORIDE - SF6

Brief Introduction of SF6 Product

Sulfur Hexafluoride(SF6) is a kind of colorless, odorless, non-toxic, and non-inflammable gas matter, with strong chemical stability, It has excellent, arc quenching properties and high electric strength, It is a sort of Super-high pressure insulation material. SF6 has a dielectric strength 2.5 nitrogen, SF6 has a breakdown voltage as oil at 0.25 Mpa. Sulfur Hexafluoride is widely used in electric equipment such as circuit breaker, airsealed combination capacitor, transformer. GIT cable, mutual inductor and lightning arrested etc. SF6 is also widely used in particle accelerator, tracer analyses, X-ray machine, nonferrous smelt and so on. It is a new super-high pressure insulation medium material after air and oil. Our products, SF6, according to purity, was classified 99.8%, 99.9% and 99.99%. According to packaging, it was classified 4 litres, 10 litres, 12 litres, 40 litres etc, kinds of steel cylinder.

Technical Specifications

ITEM UNIT(m/m) IEC-376 GB-12022-89 STANDARD
High purity Superior
Purity % 99.8 99.8 99.99 99.9
Air % 0.05 0.05 0.003 0.03
Carbon Tetrafluorid(CF4) % 0.05 0.05 0.003 0.04
Acidity(as HF) PPM 0.3 0.3 0.1 0.1
Hydrolysable Fluoride (as HF) PPM 1 1 0.5 0.5
Moisture PPM 15 8 4 5
Mineral oil PPM 10 10 4 5
Biological noxious tests . non-toxic non-toxic non-toxic non-toxic

Cylinder Information

Cylinder size Cylinder diameter (mm) Cylinder Volume (L)
3AA-2015 133 3.6
3AA-2015 178 21.6
3AA-2015 229 43.8
3AA-2265 229 43.8
3AA-2400 235 50

All cylinder are manufactured in accordance with DOT standard and have certificates issued by USA inspection organization.

Technique Speciality

molecnlar formula SF6

critical

constant

temperature 45.64
molecnlar weight 146.06 pressure 3.84Mpa
sublimatiny point -63.8°C density 725kg/m³
melting point -50.8°C mole volume 201ml/mol
dielectric constant 1.002026 (25_ 0.101Mpa)
gas density 6.16kg/m³ (20_ 0.101Mpa)
solid density 2510kg/m³ (-50_)

CAUTION

SF6 is packaged as a high voltage liquefied gas, we must carry out the strict specifications of <<The Gas Safety Inspection Procedures>> published by State Bureau of Labor in storage, transportation and usage. Store cylinders in an appropriate location, out of direct sunlight, and at temperatures no greater than 45°C. Keeping area well aired should be taken into account for storage and usage.

Inquiry/Order Form | Chemicals